Global Search

Search across sites, tenants, alerts, and pages

OP

MTN - Midrand Hub Beta

MTN · Model B · Gold SLA

Breaker ON
Total Power

9.3kW

Total Current

24.5A

Energy Today

145.1kWh

Capacity Used

93%

Phase Imbalance

1.9%

Current Limit

63A

Per-Phase Breakdown

PhaseVoltage (V)Current (A)Power (kW)% of LimitStatus
L1 (Red)233.025.003.1640%NORMAL
L2 (Yellow)230.924.303.0739%NORMAL
L3 (Blue)232.724.303.0739%NORMAL
Total24.509.30

Per-Phase Current History

No telemetry data available for this time range

Phase Balance

L1 CurrentL2 CurrentL3 CurrentL1 PowerL2 PowerL3 Power07142128
1.9% Imbalance

Capacity Utilization

93%

9.3 / 10.0 kW

12-Month Capacity Forecast

May 26Jun 26Jul 26Aug 26Sept 26Oct 26Nov 26Dec 26Jan 27Feb 27Mar 27Apr 270kW3kW6kW9kW12kW
  • Capacity Limit
  • Projected Load

Based on 2% monthly growth rate. Current headroom: 0.7 kW

Recommended Actions

1 CRITICAL
🟢

Phases Well Balanced

success

All three phases within 1.9% of each other. Maximum deviation is 0.47A from average.

Action:

No action required. Continue monitoring during load changes.

🔴

Near Capacity Limit

critical

Operating at 93% capacity with only 0.70 kW headroom. Risk of breaker trip during load spikes.

Action:

Upgrade breaker from 63A to 79A, or shed 1.4 kW of non-critical load immediately.

Power Consumption History (Site-Level)

No telemetry data available